Combustion Air/CO Study
CCHRC, through a grant from Alaska Housing Finance Corporation, conducted a combustion air evaluation in the Fairbanks area. The purpose of the study was to assess sufficiency of current practices in combustion air supply for atmospherically vented heating appliances, and assess the performance of power-vented appliances. Each house was be measured and evaluated to determine (1)house and combustion appliance zone (CAZ) surface area and volume; (2)common wall surface area and leakage; (3)air leakage of house and CAZ; and (4)the amount of combustion air (vented and ambient). CCHRC staff met with individuals who are reviewing codes for the City of Fairbanks Code Review Board and presented data collected from this study on combustion air requirements for oil-fired boilers. This information was incorporated in new code requirements and adopted as an amendment to the 2000 International Mechanical Code. Click to view the Final Report



